CHIEF – HAZARDOUS AREA

Download brochure
CHIEF - HAZARDOUS AREA

Features

The Chief is an excellent choice for Hazardous Area Lighting and is suitable for a wide range of applications. It features a low-profile, lightweight design and has an impact resistant polycarbonate clear or diffused lens. The Chief’s light distribution will project uniform illumination throughout the entire space and it’s low maintenance costs reduce power consumption by over 50%.
• Environmentally Friendly 50,000 Hours Lifetime
• Superior colour rendering index compared to HPS, LPS or MV
• Low temperature applications to -40°C and high temperature up to 55°C
• Temperature compensation technology for longer life

Typical Applications

Coal & Metalliferous Mine
Process Plants
Quarries
Campsite Area Lighting
General Area Lighting
Car Parks
Conveyors
Pedestrian Access Road Ways
Stacker/Reclaimers
Stairwells
Tunnels
Walkways
Bulkheads

    Specifications

    Model: PLICHI24 PLICHI36 PLICHI36 PLICHI50 PLICHI60 PLICHI72 PLICHI80
    Optical Characteristics
    Rated Wattage 24W 36W 36W 50W 60 72W 80W
    Lumens 2640 3960 3960 5500 6600 7920 8800
    System Efficacy 110Lm/W
    Colour Temperature CCT 5000K (6000K / 4000K / 3000K)
    CRI (Ra) >75
    Reported L70 >50,000 Hours
    Lens Optic Type 180º
    Electrical Characteristics
    Input 100-277VAC
    Frequency 50/60Hz
    Power Factor >0.95
    Total Harmonic Distortion N/A
    Environment
    IP Rating IP66
    Impact Rating IK10
    Operating Temperature -40ºC To 55ºC
    Product Material and Mounting
    Option 1 Ceiling Mount A/B
    Option 2 Wall Mount A/B
    Option 3 Pendant Pole Mount
    Option 4 Pendant Chain Mount
    Option 5 Beam Clamp Mount
    Option 6 Pole Mount
    Product Material Aluminium Housing
    Lens/Optics Material Clear Lens or Diffused Lens
    Dimensions and Weights
    Product Dimensions 385*126*88 685*126*88 1285*126*88
    Product Weight 2.8KG 4.5KG 7.5KG
    Gross Weight 4.0KG 6.0KG 9.7KG
    Warranty and Certifications
    Warranty 5 Year Warranty
    Certifications IECEx / CE / RoHS
    Classification Zone 1 & 21 / Zone 2 & 22
    Rating IECEx/Gas: II 2 G Ex eb mb op is IIC T5 T6 Gb IECEx/Dust: II 2 D Ex op is tb IIIC T80°C Db